Cold shrink cable accessories are manufactured with advanced liquid silicon rubber, which has high resilience and strength,good electrical insulation, is

UV stable and adverse to water. The cold shrink cable terminations & joints applications from 1 to 36kV(1kV, 12kV, 15kV, 20kV, 36kV). The simple installation of

cold shrink cables accessories can help you save time and physical force. It improves your work efficiency, make the cables connect safely and reliably, assure your every connection correctly sealed and insulated for long protection. So our cold shrink MV terminations & joints are widely applied in power plant (nuclear), wind farm, substations, city subway etc.


Cold Shrink Termination Kits   (for XLPE,screened armored cables)

Voltage

 Cores   

Description

Cable size

Model number

18/30kV(36)

1

Indoor 

25-50mm2

18/30kVWLN-1-1

70-150mm2

18/30kVWLN-1-2

185-400mm2

18/30kVWLN-1-3

500-630mm2

18/30kVWLN-1-4

1

Outdoor 

25-50mm2

18/30kVWLW-1-1

70-150mm2

18/30kVWLW-1-2

185-400mm2

18/30kVWLW-1-3

500-630mm2

18/30kVWLW-1-4

12/20kV(24)

1

Indoor 

50-120mm2

12/20kVWLN-1-1

150-300mm2

12/20kVWLN-1-2

400-500mm2

12/20kVWLN-1-3

630mm2

12/20kVWLN-1-4

1

Outdoor

50-120mm2

12/20kVWLW-1-1

150-300mm2

12/20kVWLW-1-2

400-500mm2

12/20kVWLW-1-3

630mm2

12/20kVWLW-1-4

8.7/15kV(17.5)

1

Indoor

25-50mm2

8.7/15kVWLN-1-1

70-120mm2

8.7/15kVWLN-1-2

150-240mm2

8.7/15kVWLN-1-3

300-400mm2

8.7/15kVWLN-1-4

1

Outdoor 

25-50mm2

8.7/15kVWLW-1-1

70-120mm2

8.7/15kVWLW-1-2

150-240mm2

8.7/15kVWLW-1-3

300-400mm2

8.7/15kVWLW-1-4

6.35/11kV(12)

1

Indoor 

25-50mm2

6.35/11kVWLN-1-1

70-120mm2

6.35/11kVWLN-1-2

150-240mm2

6.35/11kVWLN-1-3

300-400mm2

6.35/11kVWLN-1-4

1

Outdoor

25-50mm2

6.35/11kVWLW-1-1

70-120mm2

6.35/11kVWLW-1-2

150-240mm2

6.35/11kVWLW-1-3

300-400mm2

6.35/11kVWLW-1-4

0.6/1kV(1.2)

1

Indoor or Outdoor

25-50mm2

0.6/1kVWLT-1-1

70-120mm2

0.6/1kVWLT-1-2

150-240mm2

0.6/1kVWLT-1-3

300-400mm2

0.6/1kVWLT-1-4

18/30kV (36)

3

Indoor 

25-50mm2

18/30kVWLN-3-1

70-150mm2

18/30kVWLN-3-2

185-400mm2

18/30kVWLN-3-3

500-630mm2

18/30kVWLN-3-4

3

Outdoor 

25-50mm2

18/30kVWLW-3-1

70-150mm2

18/30kVWLW-3-2

185-400mm2

18/30kVWLW-3-3

500-630mm2

18/30kVWLW-3-4

12/20kV (24)

3

Indoor 

50-120mm2

12/20kVWLN-3-1

150-300mm2

12/20kVWLN-3-2

400-500mm2

12/20kVWLN-3-3

630mm2

12/20kVWLN-3-4

3

Outdoor 

50-120mm2

12/20kVWLW-3-1

150-300mm2

12/20kVWLW-3-2

400-500mm2

12/20kVWLW-3-3

630mm2

12/20kVWLW-3-4

8.7/15kV(17.5)

3

Indoor 

25-50mm2

8.7/15kVWLN-3-1

70-120mm2

8.7/15kVWLN-3-2

150-240mm2

8.7/15kVWLN-3-3

300-400mm2

8.7/15kVWLN-3-4

3

Outdoor

25-50mm2

8.7/15kVWLW-3-1

70-120mm2

8.7/15kVWLW-3-2

150-240mm2

8.7/15kVWLW-3-3

300-400mm2

8.7/15kVWLW-3-4

6.35/11kV(12)

3

Indoor 

25-50mm2

6.35/11kVWLN-3-1

70-120mm2

6.35/11kVWLN-3-2

150-240mm2

6.35/11kVWLN-3-3

300-400mm2

6.35/11kVWLN-3-4

3

Outdoor 

25-50mm2

6.35/11kVWLW-3-1

70-120mm2

6.35/11kVWLW-3-2

150-240mm2

6.35/11kVWLW-3-3

300-400mm2

6.35/11kVWLW-3-4

0.6/1kV(1.2)

3 or 4 or 5

Indoor or Outdoor

25-50mm2

0.6/1kVWLT-3(4/5)-1

70-120mm2

0.6/1kVWLT-3(4/5)-2

150-240mm2

0.6/1kVWLT-3(4/5)-3

300-400mm2

0.6/1kVWLT-3(4/5)-4


Cold Shrink Cable Joints

Use:

Cold shrink cable joint for XLPE -insulated 1 or 3 cores cables with Al or Cu conductor, 1-36kV.

Design:

The joint body is made of advanced liquid silicone rubber with three layers: a conductive outer layer, an insulating layer and a conductive inner layer.

The joints kit contains all mounting material. It improves reliability, reduces time and labor. It fits cable sizes from 25mm2 to 500mm2.


Voltage

Cores

 Cable size

Model number

18/30kV (36)

1

50-70mm2

18/30kVWLJ-1-1

95-150mm2

18/30kVWLJ-1-2

185-300mm2

18/30kVWLJ-1-3

400-500mm2

18/30kVWLJ-1-4

12/20kV (24)

1

25-50mm2

12/20kVWLJ-1-1

70-120mm2

12/20kVWLJ-1-2

150-240mm2

12/20kVWLJ-1-3

300-400mm2

12/20kVWLJ-1-4

8.7/15kV(17.5)

1

25-50mm2

8.7/15kVWLJ-1-1

70-120mm2

8.7/15kVWLJ-1-2

150-240mm2

8.7/15kVWLJ-1-3

300-400mm2

8.7/15kVWLJ-1-4

6.35/11kV(12)

1

25-50mm2

6.35/11kVWLJ-1-1

70-120mm2

6.35/11kVWLJ-1-2

150-240mm2

6.35/11kVWLJ-1-3

300-400mm2

6.35/11kVWLJ-1-4

0.6/1kV(1.2)

1

25-50mm2

0.6/1kVWLJ-1-1

70-120mm2

0.6/1kVWLJ-1-2

150-240mm2

0.6/1kVWLJ-1-3

300-400mm2

0.6/1kVWLJ-1-4

18/30kV(36)

3

50-70mm2

18/30kVWLJ-3-1

95-150mm2

18/30kVWLJ-3-2

185-300mm2

18/30kVWLJ-3-3

400-500mm2

18/30kVWLJ-3-4

12/20kV(24)

3

25-50mm2

12/20kVWLJ-3-1

70-120mm2

12/20kVWLJ-3-2

150-240mm2

12/20kVWLJ-3-3

300-400mm2

12/20kVWLJ-3-4

8.7/15kV(17.5)

3

25-50mm2

8.7/15kVWLJ-3-1

70-120mm2

8.7/15kVWLJ-3-2

150-240mm2

8.7/15kVWLJ-3-3

300-400mm2

8.7/15kVWLJ-3-4

6.35/11kV(12)

3

25-50mm2

6.35/11kVWLJ-3-1

70-120mm2

6.35/11kVWLJ-3-2

150-240mm2

6.35/11kVWLJ-3-3

300-400mm2

6.35/11kVWLJ-3-4

0.6/1kV(1.2)

 3 or 4 or 5

25-50mm2

0.6/1kVWLJ-3(4/5)-1

70-120mm2

0.6/1kVWLJ-3(4/5)-2

150-240mm2

0.6/1kVWLJ-3(4/5)-3

300-400mm2

0.6/1kVWLJ-3(4/5)-4


Performance of Cold shrink cable accessories 

SEQ.

Test Project

18/30kV(36)

12/20kV(24)

8.7/15kV(17.5)

Result

1

AC voltage

(in air and ambient
temperature)

AC for 5min. at 81kV
no breakdown, no
flashover

AC for 5min. at 54kV 
no breakdown, no
flashover

AC for 5min. at 39kV
no breakdown, no
flashover

PASS

2

Partial discharge test

≤10pc at 31kV

≤10pc at 20kV

≤10pc at 15kV

PASS

3

Impulse test

10 impulses of each polarity at

170kV

10 impulses of each polarity at

125kV

10 impulses of each polarity at

95kV

PASS

4

Heating cycle in air
(for termination )

60 cycles at 95ºC~
100ºC and 45kV in
air, no breakdown

60 cycles at 95ºC~
100ºC and 30kV in
air, no breakdown

60 cycles at 95ºC~
100ºC and 22kV in
air, no breakdown

PASS

5

Heating cycle in air
(for joints )

30 cycles at 95ºC~
100ºC and 45kV in
air, no breakdown

30 cycles at 95ºC~
100ºC and 30kV in
air, no breakdown

30 cycles at 95ºC~
100ºC and 22kV in
air, no breakdown

PASS

6

Heating cycle voltage
test under water

30 cycles at 95ºC~
100ºC and 45kV under
water, no breakdown

30 cycles at 95ºC~
100ºC and 30kV under
water, no breakdown

30 cycles at 95ºC~
100ºC and 22kV under
water, no breakdown

PASS

7

Thermal short circuit
(screen)

no visible deterioration
at current 1.97kA for 2s

no visible deterioration
at current 1.97kA for 2s

no visible deterioration
at current 1.97kA for 2s

PASS

8

Thermal short circuit
(conductor)

no visible deterioration
at current 3.0kA for 1s

no visible deterioration
at current 3.0kA for 1s

no visible deterioration
at current 3.0kA, for 1s

PASS

9

Dynamic short circuit

no visible deterioration
at current 23.0kA for 2s

no visible deterioration
at current 23.0kA for 2s

no visible deterioration
at current 23.0kA for 2s

PASS

10

AC voltage for 15 min

AC for 15 min at
45kV. no breakdown,
no flashover

AC for 15 min at
30kV. no breakdown,
no flashover

AC for 15 min at
22kV. no breakdown,
no flashover

PASS

11

Salt fog

(for outdoor

 terminations only)

1000H at 22.5kV,
no breakdown,
no flashover

1000H at 15kV,
no breakdown,
no flashover

1000H at 11kV,
no breakdown,
no flashover

PASS

12

Humidity

(for indoor
terminations only)

300H at 22.5kV,
no breakdown, no flashover

300H at 15kV,
no breakdown,
no flashover

300H at 11kV,
no breakdown,
no flashover

PASS